The main components (compressor, condenser, evaporator, and others) must be installed securely in position using the supplied brackets and in accordance with the manufacturer's instructions. The compressor should always be secured to a horizontal surface. If anti-vibration mounts are supplied, they will also be installed.
Installation of cooling system
Installation should be as fast as possible, so that a significant amount of moisture, air or other impurities have little chance of collecting in the system. Compressors and filter driers, therefore, must be installed in the past, directly in front of evacuation and charging system. All the holes in the refrigerant system is absolutely without exception, must be completely sealed from air and water vapor during any pauses that may arise in the installation works.
Installation of pipelines
To the extent possible, the tubing must be horizontal or vertical. Exceptions are:
Suction lines, which can be given a slight fall in the direction of the compressor.
Reset lines, which may have a slight fall from the compressor.
Tubes, brackets, clamps and other should be presented to suit the pipe diameter and download of the components mounted in the line.
If vibration dampers compressor is installed, then suitable vibration eliminators should be equipped with suction and discharge pipe.
Oil locks should be installed in a vertical line suction to a height of 4 to 5 meters In systems with large load variations, it may be necessary to introduce a double row. The suction line should also be set to consider the oil return to the compressor. In the systems with different load requirements are especially important at low loads.
Location of other components
All components must be installed so that they are easily accessible for maintenance and repair of equipment. Controls and safety equipment shall be located so that testing and tuning can be easily implemented using common tools...