Discharge-Bypass Valves Installation

Bypass valves can be installed in horizontal or vertical lines, whichever best suits the application and allows easy access to the valves. Note, however, by posting these valves so that they do not act as oil traps. Also solder must not run in the internal details during the soldering process.

DBV should always be installed on the condensing unit and not in the evaporator section. This will ensure the rated bypass capacity DBV. This will eliminate the possibility of hot gas condensing in the bypass line. This is especially true in remote systems.

When externally equalized line, use the equalizer connection must be connected to the suction line, where it will sense the desired operating pressure. Cm. Fig. 11-40.

Because DBV used in the bypass line between the discharge line and the low side of the system, the valve is subjected to a vibration of the compressor.

If the valve, fittings, tubing and insulated from vibration, fatigue failures may occur. While heavy valve weighs 3.5 kg (1.6 kg), it must be adequately supported to prevent excessive stress on the connection.

If the remote-lamp type bypass valve is used, the lamp must be located in a fairly constant temperature of the environment, because the lamp Assembly charged air. These valves are factory installed in 80F (27C) ambient temperature. Thus, significant deviations from this temperature will cause pressure settings that differ from the factory settings. For non-regulated valve, remote bulb may be found in the 80F 10F (27C 5.5C) adjustable remote bulb model can be adapted for work at the temperature of 80F 30F (27C 16.7C). In many parts manufacturers have modified the values of pressure to compensate for the ambient temperature significantly different than 80F (27C). Therefore, in some devices, it may be necessary to consult with the manufacturer of the equipment for the correct opening pressure setting of the relief valve

There are numerous places in the system where the remote bulb can be located. Two possible locations and return to the air flow and the structure of the device, if it is in the conditioned space. In other areas where the temperature is fairly constant, but than 80 differentF (27C) are also available. They include the return of water on cooling lines, suction line of the compressor, or the main liquid line. As mentioned earlier, the settings can be changed.

Bulb strap with nuts and bolts, as a rule, is supplied with each remote bulb type DBV. The strap for fixing the lamp to place.

..
 
Thanks ->



Application of refrigeration in chemical industry Circuit breaker Condenser Capacity Contact freezing Copper pipe sizes inches to mm Effect of superheating on cop Hermetic compressor High side of a refrigeration system Oil separator in refrigeration cycle Pressure switch Refrigeration compressor Capacity control Refrigeration cycle Refrigeration oil pressure switch wiring diagram