Home 

High efficency furnace ignition sequence

Technical information Air-Conditioning High-Efficiency Furnaces Sequence of Operation

High-efficiency Furnace, the Sequence of operations

The demand for thermal energy, the room thermostat initiates clear operation blowers for pre-purge cycle 34 C, with the subsequent switching off the ignition and the opening of the gas valve. As there is a fire, a flame sensor senses the proof of ignition and turns off the power from the spark plug and clean the fan (see Fig. 2-18). Furnace blower operation is initiated 30 to 45 seconds after combustion ignition. When the thermostat is satisfied, the gas valve is closed, and purge blower is activated for a purge at the end of the welding cycle 34 seconds. Furnace blower remains in operation until the set temperature, the setting [90F (32C)] fan control is achieved. In case of loss of flame happen until the thermostat is satisfied, a flame sensor management will hold three to five attempts to re-ignition to lock the device. In addition, the loss or combustion air intake or exhaust flue will automatically shut down the system.

..

 
Thanks ->



4 way reversing valve operation Back pressure valve in refrigeration system Capillary tube refrigeration Deep freezer Wikipedia Industrial refrigeration definition Lennox pulse 21 troubleshooting Refrigeration sight glass function Screw compressor refrigeration system Semalt com Small 2 cylinder ammonia compressor Starved evaporator Thermosyphon cooling system Vapour absorption refrigeration system Wikipedia
Copyright @ 2009 - 2022, "www.ref-wiki.com"